Two Bays Cabinet 返回上一页
Model:DDTE047
Double Wall Galvanized Steel Outdoor Telecom Cabinet With Telecom Power System, Power Distribution Unit, Sensors, AC22V Air Conditioner



DDTE047  Outdoor Telecom Cabinet Solution

Description

The cabinet includes two compartments, with separated left compartment and right compartment, and there is middle division plate between the two compartments. The left compartment is equipment compartment and the right compartment is battery compartment. The cabinet cooling uses air conditioner and fans, to ensure the equipments operate normally at stable temperature range, so as to make the service life of the equipments much longer and their performance more stable.

 

Technical Parameters

Item

  Type

 Technical Parameter

Structure

Dimension

H*W*D  2000*1600*800mm

Layout

Two compartments (left compartment and right compartment, with middle division plate).

Equipment Installation Method

19” rack

Door

With two front doors, and special lock for outdoor cabinet (support padlock)

Material

Galvanized steel; double wall

Heat Insulation

There are heat insulation between inner wall and outer wall. The insulation material is 20mm PEF.

Structure

Assembled

Ingress Protection

IP55

Temperature Control

Cooling

(AC220V air conditioner+ 48V to 220V inverter) and DC48V fans for left compartment and right compartment.

Lighting

LED lamp

48V LED lamps; The lamps will be on when the cabinet door is open, and will be off when the cabinet door is closed.

Temperature

Temperature

Working Temperature: -40°C ~ +55°C

Storage Temperature: -50°C ~ + 70°C

Transport Temperature: -50°C ~ +70°C

Humidity

Relative Humidity

5% ~ 100%

Pressure

Air Pressure

62kpa ~ 101kpa (similar to 0m ~ 5000m altitude)

Radiation Intensity

Solar Radiation Intensity

1120 ×1±5%W/m2

Lead Acid Battery Specs

The cabinet can hold maximum 3 battery strings ( each battery string is 48V 100AH).

(1) When the air conditioners are “on”:

Battery Capacity = 3h*40A/0.7=171Ah

“3h” is backup time, “40A” is (equipments + air conditioner) load, “0.7” is battery remaining

Our suggestion: use 2 battery strings ( each battery string is 48V 100AH).

(2) When the air conditioners are “off”:

Battery Capacity = 6h*20A/0.7=171Ah

“6h” is backup time, “20A” is equipments load, “0.7” is battery remaining

Our suggestion: use 2 battery strings ( each battery string is 48V 100AH).

 

Accessories List

No.

Item

Quantity

Unit

Specs

1

Two Compartment Outdoor Telecom Cabinet

1

Set

External Dimension: H*W*D 2000*1600*800mm                                                 

2

Air Conditioner

2

Set

Cooling Capacity: 1KW, AC220V; Model:TC06-100SEH/01

3

Embedded Telecom Power System

1

Set

2U, 19", 48V, 90A;

4

Inverter

2

Set

48V to 220V (for air conditioner power supply)

5

Fan

4

Set

12038, DC48V, START WORK AT 35℃

6

Power Distribution

1

Set

GRADE B LIGHTNING PROOF                 

AC INPUT: 63A/2P *1;                               

AC OUTPUT: 16A/1P*4;

DC OUTPUT: 16A/1P*4

7

Lead Acid Battery

8

Set

12V, 100AH; Model: SP12-100

8

Temperature and Humidity Sensor

2

PC

 

9

Environment Monitoring Unit

1

Set

2U

10

Door Sensor

4

PC

 

11

Water Sensor

2

PC

 

12

Smoke Sensor

2

PC

 

13

LED Lamp

2

PC

 

14

Package

1

Set

Wooden Case

 

Cabinet Layout Diagram:

 

Cooling Diagram:

Compressor Air Conditioner Cooling Diagram (The red is hot air , and the green is cold air)

 

Fan Cooling Diagram (The red is hot air , and the green is cold air)