全站搜索
轮播广告
自定内容

 
 
Product details
 
产品详情
AC220V 1300W Air Conditioner 返回上一页
AC220V 1300W Low Power Consumption Compressor Air Conditioning For Outdoor Telecom Cabinet, Base Station Room

Model:TC06-130JFH/01



AC220V 1300W Air Conditioner

Model: TC06-130JFH/01

 

1. Description
The AC Compressor Air Conditioner is a full automation temperature control product. It uses intelligent controller to control the whole system of the air conditioner. According to the variation of environment temperature, the intelligent controller can automatically detect, operate and record the whole system’s operating time, power consumption, event and historical data. It can store 100 event records and 1280 historical data records, and can enquire 256 days’ daily record information. The product is widely applied in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc. The air conditioner includes the following specs: 300W, 350W, 400W, 450W, 500W, 1000W, 1200W, 1300W, 1500W, 2000W, 2500W. In addition, it also can be custom made.

The air conditioner uses utility power input, allowing wide voltage range (±30%), with higher efficiency. The air conditioner controller is digital display temperature controller, with easy operation and straight display. The controller has 6 relay outputs, which respectively control internal circulation fans, external circulation fans, cooling compressor, heater, hydrogen exhaust fan and a reserve output way. The controller has fault detection and alarm function and can transmit fault alarm signals to monitoring center.

 

2.Features

(1)The intelligent controller with data collection function supports RS485 communication and can be connected with customers’ system;
(2)4 way DI inputs: smoke, water, door, voltage difference, shock alarm, etc.;
(3)6 way analog outputs: temperature and humidity, voltage, current, AC detection etc.;
(4)Can work together with telecom room air conditioner and set operating range;
(5)Two way DO programmable output:: general alarm output or other parameters output;
(6)Used for outdoor cabinet temperature control, energy saving and optimized efficiency;
(7)Storage: can store 200 equipment working information and 2000 history record data;
(8)Two way temperature and humidity collection channels: collecting temperature and humidity of thermostatic cabinet and base station;
(9)Regular hydrogen exhaust ; 
(10)Sensors, fans, compressor fault detection function; environment temperature and humidity, equipments fault alarm function.

 

3. System Principle Diagram

 

4. Standard Compliance

 

 

 

 

5.Technical Parameters

 


 

6. Electrical Wiring Diagram


Wiring Ports:

L N PE : power supply port (input voltage 220VAC±25% 50/60Hz)
0V 48V: power supply port for hydrogen exhaust fan (input voltage:38-58VDC)
F+ F- : hydrogen exhaust fan control port
A+ B- : RS-485 communication interface
S5V S D W ALARM N N : 5V power supply, smoke sensor, open door alarm, water sensor, general alarm output, 5V power ground pin, not connected pin.


7.System Control Board

Technical Parameter

a.LCD display, user friendly; 
b.Simultaneously display temperature and humidity inside the cabinet and communication room temperature; 
c.Temperature measurement accuracy: 0.1 °C; humidity measurement accuracy:5%;
d.Can store 180 days’ daily event record, 1 record every day;

e.Daily highest temperature, lowest temperature, average temperature
f.Daily event record;
g.Store the former day’s daily data at 0:00 every day; Can enquire 180 days’ daily record information;
h.RS485 communication,RTU-Modbus protocol, support remote detection and control;
i.Controllable air conditioner quantity:2 sets. 1 set of air conditioner for communication room, and 1 set of small air conditioner for thermostatic cabinet.
j.Control mode: pulse (Non dry contact air conditioner), conducting (dry contact air conditioner)
k.Real-time control air conditioner on/off
l.Power supply: AC85V~265V/50HZ;
m.Power consumption:≤5W;
n.Working environment: -30°C~70°C;<90%RH;
o.Installation method: guide rail,hanging;
p.Dimension:150mm×190mm×45mm

 


8. Wiring Diagram