IP55 19 Inch Rack thermostatic Outdoor Telecom Cabinet For Base Station
DDTE044 Outdoor Telecom Cabinet Solution
Description
The cabinet includes one compartment. The cabinet cooling uses air conditioner and fans, to ensure the equipments operate normally at stable temperature range, so as to make the service life of the equipments much longer and their performance more stable.
Technical Parameters
Item
Type
Technical Parameter
Structure
Dimension
External Dimension H*W*D 2000*800*800mm
Internal Dimension H*W*D 1800*700*700mm
Layout
One compartment
Equipment Installation Method
19” rack
Door
With one front door, with special lock for outdoor cabinet (support padlock)
Material
Galvanized steel; double wall, thickness of outer plate: 1.5mm, thickness of inner plate: 0.8mm.
Heat Insulation
There are heat insulation between inner wall and outer wall. The insulation material is 20mm PEF.
Structure
Welded
Ingress Protection
IP55
Temperature Control
Cooling
1500W, AC220V air conditioner + 48V to 220V inverter; and DC48V fans
Lighting
LED lamp
48V LED lamps, when the door is open, the LED lamp will turn on; when the door is closed, the LED lamp will turn off.
Temperature
Temperature
Humidity
Relative Humidity
5% ~ 100%
Pressure
Air Pressure
62kpa ~ 101kpa (similar to 0m ~ 5000m altitude)
Radiation Intensity
Solar Radiation Intensity
1120 × (1±5%)W/m2
Lead Acid Battery Specs
The cabinet can hold maximum 3 battery strings ( each battery string is 48V 100AH).
(1) When the air conditioner is “on”:
Battery Capacity = 3h*40A/0.7=171Ah
“3h” is backup time, “40A” is (equipments + air conditioner) load, “0.7” is battery remaining
Our suggestion: use 2 battery strings ( each battery string is 48V 100AH).
(2) When the air conditioners are “off”:
Battery Capacity = 6h*20A/0.7=171Ah
“6h” is backup time, “20A” is equipments load, “0.7” is battery remaining
Our suggestion: use 2 battery strings ( each battery string is 48V 100AH).
Accessories List
No. |
Item |
Quantity |
Unit |
Specs |
1 |
Outdoor Telecom Cabinet |
1 |
Set |
External Dimension H*W*D 2000*800*800mm |
2 |
Air Conditioner |
1 |
Set |
Cooling capacity: 1500W, Power Supply: 220V; Model: TC06-150JFH/01 |
3 |
Embedded Telecom Power System |
1 |
Set |
1U, 19", 3000W, DC48V,60A |
4 |
Inverter |
1 |
Set |
48V to 220V (for air conditioner power supply) |
5 |
Fan |
2 |
Set |
12038, DC48V, START WORK AT 35°C |
6 |
Power Distribution |
1 |
Set |
GRADE B LIGHTNING PROOF AC INPUT: 63A/2P *1; AC OUTPUT: 16A/1P*4;
DC OUTPUT: 16A/1P*4 |
7 |
Lead Acid Battery |
8 |
Set |
12V, 100AH, Model: SP12-100 |
8 |
Temperature and Humidity Sensor |
1 |
PC |
|
9 |
Environment Monitoring Unit |
1 |
Set |
2U |
10 |
Door Sensor |
2 |
PC |
|
11 |
Water Sensor |
1 |
PC |
|
12 |
Smoke Sensor |
1 |
|
|
13 |
LED Lamp |
1 |
PC |
DC48V |
14 |
Package |
1 |
Set |
Wooden Case |
Cabinet Layout Diagram:
Cooling Diagram:
Compressor Air Conditioner Cooling Diagram (The red is hot air , and the green is cold air)
Fan Cooling Diagram (The red is hot air , and the green is cold air)