全站搜索
轮播广告
自定内容

 
 
Product details
 
产品详情
One Bay Cabinet 返回上一页
Model:DDTE044
IP55 19 Inch Rack thermostatic Outdoor Telecom Cabinet For Base Station



DDTE044 Outdoor Telecom Cabinet Solution

Description

The cabinet includes one compartment. The cabinet cooling uses air conditioner and fans, to ensure the equipments operate normally at stable temperature range, so as to make the service life of the equipments much longer and their performance more stable.

 

Technical Parameters

Item

  Type

 Technical Parameter

Structure

Dimension

External Dimension H*W*D  2000*800*800mm

Internal Dimension H*W*D   1800*700*700mm

Layout

One compartment

Equipment Installation Method

19” rack

Door

With one front door, with special lock for outdoor cabinet (support padlock)

Material

Galvanized steel; double wall, thickness of outer plate: 1.5mm, thickness of inner plate: 0.8mm.

Heat Insulation

There are heat insulation between inner wall and outer wall. The insulation material is 20mm PEF.

Structure

Welded

Ingress Protection

IP55

Temperature Control

Cooling

1500W, AC220V air conditioner + 48V to 220V inverter; and DC48V fans

Lighting

LED lamp

48V LED lamps, when the door is open, the LED lamp will turn on; when the door is closed, the LED lamp will turn off.

Temperature

Temperature

Working Temperature: -40°C ~ +55°C

Storage Temperature: -50°C ~ + 70°C

Transport Temperature: -50°C ~ +70°C

Humidity

Relative Humidity

5% ~ 100%

Pressure

Air Pressure

62kpa ~ 101kpa (similar to 0m ~ 5000m altitude)

Radiation Intensity

Solar Radiation Intensity

1120 × (1±5%)W/m2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lead Acid Battery Specs

The cabinet can hold maximum 3 battery strings ( each battery string is 48V 100AH).

(1) When the air conditioner is “on”:

Battery Capacity = 3h*40A/0.7=171Ah

“3h” is backup time, “40A” is (equipments + air conditioner) load, “0.7” is battery remaining

Our suggestion: use 2 battery strings ( each battery string is 48V 100AH).

(2) When the air conditioners are “off”:

Battery Capacity = 6h*20A/0.7=171Ah

“6h” is backup time, “20A” is equipments load, “0.7” is battery remaining

Our suggestion: use 2 battery strings ( each battery string is 48V 100AH).

 

Accessories List

No.

Item

Quantity

Unit

Specs

1

Outdoor Telecom Cabinet

1

Set

External Dimension H*W*D  2000*800*800mm

2

Air Conditioner

1

Set

Cooling capacity: 1500W,  Power Supply: 220V; Model: TC06-150JFH/01

3

Embedded Telecom Power System

1

Set

1U, 19", 3000W, DC48V,60A

4

Inverter

1

Set

48V to 220V (for air conditioner power supply)

5

Fan

2

Set

12038, DC48V, START WORK AT 35°C

6

Power Distribution

1

Set

GRADE B LIGHTNING PROOF  

AC INPUT: 63A/2P *1;                                            

AC OUTPUT: 16A/1P*4;                  

DC OUTPUT: 16A/1P*4

7

Lead Acid Battery

8

Set

12V, 100AH, Model: SP12-100

8

Temperature and Humidity Sensor

1

PC

 

9

Environment Monitoring Unit

1

Set

2U

10

Door Sensor

2

PC

 

11

Water Sensor

1

PC

 

12

Smoke Sensor

1

 

 

13

LED Lamp

1

PC

DC48V

14

Package

1

Set

Wooden Case

 

Cabinet Layout Diagram:

 

Cooling Diagram:

Compressor Air Conditioner Cooling Diagram (The red is hot air , and the green is cold air)

Fan Cooling Diagram (The red is hot air , and the green is cold air)

脚注信息

 